![]() Missing EIC values in analogue delta alarms have been added."Remote start and close GB" and "Remote open GB and stop" functionalities have been improved.Initiated cool-down cannot be aborted when a wire-break fail class alarm is present.Different alarm fail classes can now be selected through #4066.M-Logic commands for selecting AC configurations added.An alarm now appears if the M-Logic data is corrupted.Analogue input sampling has been updated in order to improve the precision.Scaling range has been changed from 1 kV-75 kV to 0.4 kV-75 kV.Selection of used frequency for alarm trip added.“Frequency Detection Level” (parameter 6165) added.“External Engine Stop” detection (parameter 6342) added.“Running Detection Reached” timer (parameter 6341) added.Be sure to configure the before mentioned, if you have been using this feature prior to this software update. The feature is now enabled or disabled from the USW. Start and stop threshold can now be configured as high or low alarm. ![]() Firmware upgrade over TCP/IP has been enabled.Fixes Modbus TCP connection (option N), when an engine protocol is selected on CAN Engine Interface Communication (option H7).Starter now deactivates when the "Remove starter" threshold is reached during start sequence.Version 3.22.2 based on version 3.22.1 Correction: Configurable Modbus area works correctly even though no DU-2 is mounted.Translation now works even though no DU-2 is mounted AND only new language is written.Version 3.22.3 based on version 3.22.2 Correction: